Understand and convert Delta T radiator outputs

Delta T is the difference between the radiator's mean water temperature and the room temperature. Use the converter to compare published outputs with your heating system.

Delta T Conversion

B2-EN442 states all hydronic radiator and towel rail outputs are tested and presented at Delta T 50° / ΔT 50° as standard. To calculate the output at a different Delta T, complete the form below and select your required Delta T conversion.

Delta T correction-factor tables

Hydronic radiator outputs are normally compared at ΔT50. Lower-temperature systems produce less heat from the same radiator, while higher Delta T systems produce more. These rounded reference values support quick comparisons for modern boilers, heat pumps and older high-temperature systems.

Outputs quoted at ΔT50

Multiply output quoted at ΔT50 by the factor shown.

Required Delta TCorrection factor
ΔT50.05
ΔT100.12
ΔT150.21
ΔT200.3
ΔT250.41
ΔT300.51
ΔT350.63
ΔT400.75
ΔT450.87
ΔT501
ΔT551.13
ΔT601.27
ΔT651.41
ΔT701.55
ΔT751.69

Outputs quoted at ΔT60

Multiply output quoted at ΔT60 by the factor shown.

Required Delta TCorrection factor
ΔT150.185
ΔT200.262
ΔT250.344
ΔT300.43
ΔT350.519
ΔT400.605
ΔT450.705
ΔT500.787
ΔT550.906
ΔT601

Worked examples

A radiator producing 1,000 Watts at ΔT50 produces 750 Watts at ΔT40: 1,000 × 0.75.

An output quoted as 1,000 Watts at ΔT60 converts to 787 Watts at ΔT50: 1,000 × 0.787.

Use manufacturer-certified output data where available. A heating professional should confirm radiator sizing and system temperatures.

Need to size a room?

Use the BTU calculator on a radiator collection to calculate the room requirement and see adequately sized products.